Schmeg.com
     
 


 
Schmeg.com

Adding Subpanels

Schmeg  Home Improvement  >  Electric Service (part 2)
 
Electric Service:

      

ADDING ON SUBPANELS:
If your main service panel is full and you wish to add circuits, you may want to install a subpanel. Before you begin, check local codes. Then proceed as follows:

  1. Switch all main circuit breakers to OFF or remove all main fuses. Remember, incoming power cables and connections to main breakers or switches are still "live" even though the mains have been turned off. Remove the font cover.
  2. The supply wires coming into the subpanel must be protected at their point of supply by installing a properly sized circuit breaker or fuse. The ampere rating of the protecting breaker or fuse cannot exceed the rating of the subpanel being installed. Branch circuit wire sizes and breaker ratings must also conform to code requirements.
  3. Remove the front cover of the subpanel.
  4. Select the cable clamps approved for the wire or cable sizes used.
  5. Before removing any knockouts, determine where the wiring must enter and exit the sub panel box and also determine the size knock out required based on the diameter of conduit hub or cable clamp being used. Remove only those knockouts needed for wiring.
    To remove the 1/2" knockouts, place a nail set on either side and give the tool a sharp rap with a hammer to the edges inward. From inside the main service panel, grip the bent edges of the knockout with pliers and work them back and forth until the knockout comes off.
    Some panels have multisection knockouts for 6 and 8 gauge 240-volt lines. In such a panel, remove the center, like you did for the 1/2" knockout, then pry up the next ring using a heavy screwdriver levered on a pair of pliers. Grip the pried-up edges of the ring with the pliers from outside the panel and pull off the ring. To complete the opening, tap the last ring inward and remove it with the pliers from inside the panel.
    According to code regulations, all unused, open knockout holes must be closed. Filler plugs are available from your electrical supplier for this purpose.
  6. The subpanel may be flush or surface mounted on a wall as you desire. To flush mount a subpanel in a recess within a wall, remove the small oval knockouts in the box sidewalls. Position the box between the wall studs so the front edge of the box will be even with the wall surface. Fasten the box to studs with nails or screws through the small knockouts.
    To surface mount a panel on a wall, fasten it with screws or nails (or other mounting devices appropriate for the type of wall construction) through the mounting holes in the back of the subpanel.
  7. Once the wiring for the new branch circuit is completed, cut the wire allowing sufficient length for panel installation. (Remember that excess wire can easily be cut away, but adding on to it is prohibited by code). Install the cable clamps or conduit and bushings in knockouts to protect the wire insulation. Tighten the locknut. Pull the wire in the subpanel far enough to allow for the longest connection. Working in the panel, pass the inner connector ring over the wires and screw the connector together, allowing only enough cable sheathing to enter the panel to give purchase to the connector. Tighten the connector's toothed inner ring using a screw driver and hammer, then tighten the screws on the connector outside the panel.
  8. To prepare copper supply wire or feeder cable, cut it into individually required lengths. Carefully strip off only enough insulation to allow the wire to be fully inserted in the terminal.
    To prepare aluminum supply wire, once it has been stripped, wire-brush the exposed ends and immediately coat them with a UL-listed conductor termination compound. This compound, available from your electrical supplier, is an oxide inhibitor.
    CAUTION: Do not connect aluminum wires to the subpanel or breaker unless they are marked CU/AL. Some subpanels and breaker terminals are suitable for copper wire only.
  9. The wires supplying the panel must be protected at the point of supply by a properly sized breaker in accordance with code requirements. To connect the supply lines, loosen the terminal screws, connect the bare copper or aluminum or green equipment wire to the equipment ground bar. Do not attach the equipment ground wires to the neutral bar in the subpanel. (A ground bar accessory kit can be purchased from your local electrical supplier. The proper ground bar kit series number can be obtained from the label on the inside of the subpanel door). Connect the white neutral sup ply to the neutral supply wire to the neutral bar.
    Connect the black and/or red supply wires to the power supply terminals. Tighten all terminal screws securely. If a torque is specified on the subpanel label, use a torque wrench to tighten the terminal screws.
  10. To install the breakers, switch it to the OFF position. Loosen the breaker terminal screws. Tilt the breaker. Slide the breaker onto the hook strip and firmly press it onto the load center tab. Make sure the newly installed breaker is pushed inward until fully seated.
  11. To prepare the branch circuit wires, cut wires to individually required lengths. Carefully strip off only enough insulation to allow the wire to be fully inserted into the terminal.
  12. To connect the branch circuit wires, follow the same procedure as given in step 10.
  13. Remove only as many knockouts from the subpanel cover as required to create openings for the breaker. If any are inadvertently removed, fill the unused openings in the cover with filler plates that are available from your local electrical supplier.
  14. Replace the subpanel front cover.
  15. Identify all branch circuits. Attach the directory label to the inside of the cover or door.
  16. Have your local electrical inspector check a new installation before it is energized. Be sure the new branch breakers are in the OFF position. Restore power to the circuit supplying the subpanel. One at a time, switch the new breakers or fuses to the ON position. If the breaker trips or the fuse blows, do not reset or replace it until the condition causing the problem is fixed. Turn the power off and recheck. If you can't find the problem, consult an electrician.

<< Prev

Schmeg Home
copyright © 2010 Schmeg.com